★Digital input signal: passive pulse or level signal, the minimum duration of pulse signal is 100ms;
★ Analog output signal∶4~20mA position signaal; load resistance ≤750Ω; temperature influence ±0.1%/10K;
★ Switch output signal:K1~K6;relay output,contact rated capacity: 5A@250VAC, 5A@30VDC;★The analog output and switch input channelsare all photoelectrically isolated, and the analog output has short circuit protection;
★ Fieldbus control: support PROFIBUS-DPVO/DPV1,MODBUS,CANopen,etc.;★ Adjusting times: starting times can reach 600 times/hour;★Motor insulation level:F;★Motor working system: S2;★Basicerrorlimit:≤±1.0%;★Return difference:≤1.0%;
★Repeatability error of stroke control mechanism:≤1.0%;★Protection level:IP67(IP68 optional);
★ Explosion-proof type: Explosion-proof grade Exd ll BT4.